Software company near Walldorf | St. Leon Rot

Refurbishment cooling towers

Europe’s largest software company near Walldorf operates the central ROT07 combined heat and power plant at its St. Leon-Rot site to generate electricity, heating and air-conditioning chilled water. In addition to the various heat generation plants, cooling generation plants are also installed.

6 open cooling towers were replaced with new units with a total cooling capacity of 10 MW and the heat generation and cooling systems were refurbished. Peripheral plant components were also adapted and renewed and the new cooling tower system was connected to the existing re-cooling system. For the correct water volume distribution to the drycoolers, new throttle valves were installed and the steel substructure was completely replaced and built up according to the static requirements of the new drycoolers.

 

Dimensions and weights per cooling tower without silencer:

  • Length: 4,3 m
  • Width: 4,4 m
  • Height approx.: 7,675 m
  • Unladen weight: 7,750 kg
  • Operating weight: 14,500 kg

 

Performance data per cooling tower:

  • Water volume flow: 241 m³/h
  • Dissipated heat: 1,667 kW
  • Water inlet temperature: 34.0 °C
  • Water outlet temperature: 28.0 °C
  • Wet bulb temperature: 24.0 °C
  • Required nozzle inlet pressure: 0.3 bar
  • Evaporation water flow rate: 2.5 m³/h
  • Volume of blowdown water to be discharged at EZ=3 according to VDI3803: 1.2 m³/h

20220921_134640

Kühltürme

20220921_134640

Kühltürme

20220921_134702

Kühltürme

20220921_134728

Kühltürme

20220921_144456

Kühltürme

20220921_144508

Kühltürme

20220921_144513

Kühltürme